Ventcroft Enhanced Fire Performance Cables

 






Red Enhanced Fire Cable

 

Many schools, collages, public buildings or where the very best protection is required, now demand the 2 hour duration provided by an 'Enhanced' Fire Cable. NoBurn Diamond Enhanced meets this requirement and is approved by LPCB to the 'Enhanced' standard of BS5839-1 2002 +A2:2008 Clause 26.2e Enhanced and also the requirements of BS8434 - 2:2003 120 minutes and BS EN 50200 Class PH120.

NoBurn Diamond's Firelok design adds simple but effective strength and makes NoBurn Diamond cable the fastest enhanced cable to install and prepare for installation. The outer sheath and foil are adhered so together are removed at the same time, no time consuming multiple sheaths, foils, wraps or mica tapes to remove.

More flexible than most enhanced fire cable, NoBurn Diamond stays where you put it - simple and easy to dress and position in conduit or trunking.

NoBurn cores are manufactured with multiple twists to provide the highest level of data protection , ideal  for long cable runs and analogue addressable fire systems. NoBurn softskin enhanced fire cable provides a cost effective quick to install alternative to MICC cables.

Also suitable for automatic lift doors, air conditioning and computer control  where low smoke, fume and zero halogen cable is required. 

 

 Features

Fastest Enhanced Fire Cable to Prepare for Termination
Easy to Install and Superb Working Flexibility
Twisted Cores to Provide High Level Data Protection
Full Size CPC (Earth Core)
Red and White Outer Sheaths Available
1mm²,1.5mm² & 2.5mm²
500 Metre and Special Lengths Available
Copper / Co-polymer Foil Screen
 Approved and Certified to meet

BS 5839-1:2002 +A2:2008 Clause 26.2e

'Enhanced' Fire Cable
BS 8434-2:2003 +A2:2008 120 mins Fire Resistance Standard
BS EN 50200:2006 PH120 Fire Resistance Standard
BS 7629-1:2008 Fire Resistance Standard
BS 6387:1994 Clause 11 CWZ Fire Resistance Standard
BS EN 50267-2-1:1999 Halogen Emission Standard
BS EN 61034-2:2005 Low Smoke Standard
 Also Approved For
Emergency Lighting Standard BS 5266-1:2005
Voice Alarm Systems Standard BS 5839-8:2008
Voice Communication Standard BS 5839-9:2003

back to top

Accreditations and third Party Certification



LPCB Product Certification




LPCB Quality Management
ISO9001:2000 Certification

 

back to top

Ventcroft Firelok Design


NoBurn Diamond's design removes overlap vulnerability, reduces accidental damage and minimises the potential for water ingress due to overlap failure during fire conditions.

 

 Manufacturers Recommended Installation Guide Lines


Recommended metal clip spacing 300mm Horizontal, 400mm Vertical

Installation Temperatures:
Minimum installation Temperature
0ºc
Maximum installation Temperature 70 C

Operating Temperature Temperature:
Minimum -40 C to Maximum +90 C

The cable should not be flexed or bent when either the cable or operating temperature is below the recommended installation temperatures.

Minimum Bend Radius = 6 x Diameter
Plastic Clips or ties must not be used as the sole means of support for fire cable.

 

back to top

BS5839, Part 1:2002 Update

A recent amendment to BS5839, (fire detection and fire alarm systems for buildings - Code of practice for system design, installation, commissioning and maintenance) has been issued. The new Standard BS5839 Part 1:2002 details many revisions but in particular the use and standards of Fire Performance Cables.

More Information

back to top

Downloads

The download drop down box allows you to download files for the products on this page. Files include, Instruction Manuals, Sales leaflets, Specifications and Certificates. Adobe Acrobat Reader may be required to read some of the file, a link is included to download the reader if you require it.Get Adobe Reader


 

back to top

Ventcroft Enhanced Fire Performance Cable

         Red

Red 1.5mm Cores & CPC Earth

Reel Cores Code Pallet Min Qty Trade Per 100m

 

 

 

 

1.5mm

100m 2 Cores & CPC VEP-215ERH 60 1 TBA

1.5mm

100m 3 Cores & CPC VEP-315ERH 60 1 TBA

1.5mm

100m 4 Cores & CPC VEP-415ERH 60 1 TBA

1.5mm

200m 2 Cores & CPC VEP-215ERH200MWR 20 1 TBA

1.5mm

200m 4 Cores & CPC VEP-415ERH200MWR 20 1 TBA

1.5mm

500m 2 Cores & CPC VEP-215ERH500MWR 10 1 TBA

1.5mm

500m 4 Cores & CPC VEP-415ERH500MWR 10 1 TBA

Red 2.5mm Cores & CPC Earth Reel Cores Code Pallet Min Qty Trade Per 100m

2.5mm

100m 2 Cores & CPC VEP-225ERH 60 1 TBA

2.5mm

200m 2 Cores & CPC VEP-225ERH200MWR 20 1 TBA

2.5mm

500m 2 Cores & CPC VEP-225ERH200MWR 10 1 TBA

*Cable prices will vary due to changes to copper costs*

back to top

Fire Performance Cable Part Code Break Down

VFP-215ER

VEP - 2 15 E R H  
Product Type   Conductors CSA CPC Type Outer Sheath Colour Core Colours Length
Ventcroft Fire Performance
Cable "NoBurn Diamond"

 

  2 - 2 Core

4 - 4 Core

10 - 1.0mm

15 - 1.5mm

25 - 2.5mm

E - CPC & Screen
 
R - Red

W - White

H- Harmonised Colours

- Old Colours

 

- 100M

50 - 50M

500 - 500M

750 - 750M

(M = Meter)

 

 Revised:14/04/2010

 
 