LED's
Green Power LED
-In normal operation when the mains is applied the green power LED is illuminated.
Yellow Fault LED (Premium Model only)
- When utilizing the monitored fire input facility if the monitored circuit is removed the Fault LED
will Illuminate.
- If the internal fuse blows the Orange fault LED will flash.
Red Activated / Relay Operated
- When the relay is activated the Red Operated LED Is Illuminated.
- During delayed class change input the Red LED with Flash until the Relay is operated. (Premium
Model Only)
Internal Buzzer (Premium Model Only)
Manual Key Switch Release
- Momentary Release = Rapid Bleep 4 per second.
- latched Release = Slow bleep , 1 per 10 seconds.
Fire Input Switch Input Release
- Activation = 2 bleeps per seconds
- Class Change Delay = Bleeps Increase until door release. (Premium Model Only)
Switch Remote Release.
- Activation = 2 bleeps per seconds
Monitored Fire Input Fault Release
- When the monitored input is interrupted the buzzer will make a constant tone.
Front Mounted Mute / Door Release Key Switch
In Normal operation turn key switch 90 deg clock wise for 0.5 second and return key switch to rest ,
the relay is changes for 5 seconds and doors are released.
To latch relay and prevent the door(s) from being held open first release the doors and return the
key switch to reset then turn the key switch back to release within 1 second, the relays is now
latched until the key switch is returned back to rest.
Selectable Jumpers (Premium Model Only)
Class Change
Off - No Class Change
Fault
0ff - On -
Class Change Feature (Premium Model Only)
During an Input Fire input the door release is delayed for 10 seconds, and is only released after the 10 seconds of
constant input. If the input is removed during the delay time the door release will not active and the delay timer is
reset.
- Apply Class change input
|