Detector Base Wiring

 
  Nittan Hochiki Apollo Ziton
  Standard
Base
Resister Base Diode Base Diode/Resister Base YBO-R/5ZD YBN-R/6SK YBN-R/4 Series 60 Standard Base
Diode Base Common Base
Positive In 3 4 3 4 1 1 1 L1 IN L1 IN 5
Positive Out 3 4 3 4 2 2 2 L1 OUT L1 OUT 5
Negative In 1 1 1 1 5 5 5 L2 L2 3
Negative Out 6 6 6 6 6 6 6 L2 L2 2
Remote Indicator Positive 4 4 4 4 1 1 n/a L1 IN L1 IN 5
Remote Indicator Negative 5 5 5 5 3 4 n/a -R -R 8
End - of - Line Terminating Device End-Off- Line
Resister
End-Off- Line Resister Active
End Of Line Device
Active
End Of Line Device
End-Off- Line Resister Active
End Of Line Device
End-Off- Line Resister Active
End Of Line Device
End-Off-Line Resister End-Off-Line Resister
Head Removal

Supported

No No Yes Yes Yes Yes No Yes No No