Wiring FF502P
4 Sounder Circuit Expander
Wiring a C-Tech FF502P 4 Sounder Circuit Expander to Ventcroft FT4/8BS Fire Panels
 
Wiring
FF502P FT4/8BSA
 
AUX24 Aux 24 +
0V Aux 0 -
 
SNDR -VE Sounder +
SNDR +VE Sounder -
 
End Of Line Resister
The Supplied 6K8 Sounder circuit end of line monitoring resister should be fitted accores the SNDR -VE and  the SNDR +VE withing the FF502P Sounder expander unit.
 
Jumpers
The PLK3 Link must be removed before testing other wires the control panel will produce a fault

 

 